We have been using this inverter now for 3 months and it has been great. We upgraded our previous system with an EG4 system and have been super happy so far. Love the touch screen on the unit and remote monitoring when away. Had a hiccup during hookup and Fern and everyone at Current Connected were awesome in helping us trouble shoot and get up and running quickly being off-grid, and answering any questions we had. Incredible service. Will definitely buy from Current Connect again when adding to our system in future.
EG4 18kPV-12LV All-in-One Hybrid Solar Inverter, 12kW 48V Split Phase 120/240V, 18kW PV Input, 3 MPPT, 200A Bypass, UL 1741 SB
SKU: EG4INV18KPV00






Log in to check member price and detailed stock information.
| Need more than what's available? Tell us what you need and we can source it for you. |
Product Summary
The EG4 18kPV is a 48V all-in-one hybrid inverter that sells solar back to the grid, carries your home through outages, or runs fully off grid. Solar charge control, a PV disconnect, battery and load breakers, and a generator input are all built in, so one wall-mounted unit does the job of a whole rack of separate parts.
Specifications:
- 12kW continuous at 120/240V split phase (10.4kW at 120/208V), surging to 15.5kW for 5 minutes on solar
- 18kW of usable solar on three MPPTs, 600Vdc max input, 140 to 500Vdc operating range
- MPPT 1 takes two strings (25A usable, 31A short circuit); MPPTs 2 and 3 take one string each (15A usable, 19A short circuit)
- 250A charge and discharge on 48V lithium or lead acid batteries (40 to 60Vdc)
- 200A grid bypass and a 90A generator input with 2-wire auto start
- Built-in rapid shutdown, AFCI (Arc Fault Circuit Interrupter), PV disconnect, and 200A battery and load breakers
- Certified to UL 1741 SB, IEEE 1547 and California Rule 21, in a NEMA 4X outdoor enclosure
- 34.3×20.5×11.2 in (870×520×285 mm), 121 lb (55 kg), Wi-Fi dongle included, 10-year warranty
Current Connected is YOUR EG4 Electronics product specialist

About the EG4 18kPV Hybrid Inverter
The EG4 18kPV is an all-in-one hybrid solar inverter that puts solar, batteries and the grid under one roof. It sells extra solar back to the utility, keeps the house running when the grid goes down, or powers a property with no utility at all, and it can handle grid-tie and off-grid duty at the same time.
Everything between your panels and your loads lives inside: three MPPT charge controllers, the battery charger, a PV disconnect, battery and load breakers, a generator input and a 200A bypass. You hang one unit, land your conductors, and set it up from the front display or the EG4 app.
Room to grow is built in too. Up to 10 units run in parallel for 120kW, and the included Wi-Fi dongle connects each one to EG4's monitoring app and website for live solar, battery and grid data plus remote setting changes.
18kW of Solar Across Three MPPTs at Up to 600Vdc
The 18kPV uses up to 18kW of solar, and EG4 recommends up to 21kW of panels on it, which leaves room to oversize the array. High string voltage (up to 600Vdc) also means smaller PV wire on long runs out to a ground mount or barn roof.
MPPT 1 has two inputs and 25A of usable current, while MPPTs 2 and 3 take one string each at 15A. That makes it easy to put east, west and south faces on their own trackers. Size strings to stay under 600Vdc on the coldest morning of the year, since EG4 does not cover damage from inputs above 600Vdc under warranty.
12kW Split Phase Output With Surge for Well Pumps and Welders
The 18kPV delivers 12kW continuous at 120/240V split phase, enough to run a range, a dryer and a well pump at once. In backup mode each 120V leg carries up to 8,000W, which gives unbalanced 120V loads plenty of room.
For motor starts, it surges to 14.7kW for 10 minutes or 15.5kW for 5 minutes with solar available (13.5kW for 10 minutes on battery alone), backed by a 180A locked rotor amp rating. EG4 has filmed its smaller 12kPV starting a 5-ton A/C unit, and the 18kPV brings 50% more continuous output to the same job. That headroom covers welders, air compressors and well pumps as well.
Output is pure sine wave with under 5% THD, so sensitive electronics run clean. Idle draw is about 70W in normal mode and 18W in standby.
200A Grid Pass-Through and a Built-In Generator Input
The grid input passes up to 200A through to the load side, enough to feed a full 200A main panel rather than a small critical loads subpanel. When the grid drops, the 18kPV carries that panel on solar and battery up to its 12kW rating.
A separate 90A generator input lets a backup generator charge the batteries and carry loads with no external transfer switch. Already have a grid-tied array? The generator port also accepts AC coupling, so an existing system such as Enphase IQ8 microinverters can charge the 18kPV's batteries with up to 21.6kW (90A) of AC power.
UL 9540 Battery Pairings and 250A Charging
The 18kPV charges and discharges at up to 250A on 48V lithium or lead acid batteries, and EG4 recommends at least 300Ah of battery per inverter. Closed-loop communication over CAN or RS485 lets the inverter follow the battery's own charge limits instead of fixed voltage settings.
Many AHJs (Authority Having Jurisdiction) require a UL 9540 listed energy storage system, which covers the inverter and battery tested together. EG4 holds UL 9540 listings for the 18kPV paired with the EG4 WallMount All Weather 280Ah battery, the WallMount Indoor 280Ah, the CAB LL and the CAB LifePower4 v2.
Rapid Shutdown and UL 1741 SB Grid Compliance
Rapid shutdown is built in to meet NEC 690.12. Press the button on the unit and PV conductor voltage drops below 30V within 30 seconds, and with supported EG4 batteries on closed-loop communication, the battery bank disconnects too. Tigo lists the 18kPV-12LV as compatible with its TS4 rapid shutdown modules, including the Tigo TS4-A-F.
For a shutdown station by the meter or the door, wire a normally open E-stop to the RSD terminals. The IMO Rapid Shutdown Initiator has the normally open contact this calls for. On the grid side, the 18kPV is certified to UL 1741 SB, IEEE 1547 and California Rule 21, with arc fault (UL 1699B) and ground fault protection built in.
Mounting, Clearances and Battery Cable Sizing for the 18kPV
The NEMA 4X enclosure is rated for outdoor use from -13°F to 140°F (-25°C to 60°C), but EG4 says to keep it out of direct sunlight, so pick a shaded wall, a carport or a shed. Leave at least 7.9 in (20 cm) of clearance on every side for cooling, and plan on two people to hang the 121 lb (55 kg) unit. Above 6,561 ft (2,000 m) the output derates, so check EG4's altitude guide for mountain installs.
EG4 specifies battery cables as two sets of 1/0 AWG up to 10 ft, two sets of 2/0 AWG up to 20 ft, one set of 4/0 AWG up to 10 ft, or one set of 250 kcmil up to 20 ft. Torque 1/0 and 2/0 lugs to 165 in-lb and 4/0 to 275 in-lb. Our custom battery cables are built to your length in 6 AWG to 4/0 AWG, and the EG4 Conduit Box joins the 18kPV to a WallMount battery with the wiring hidden.
Grid and load terminals take 6 AWG to 4/0 AWG at 95 to 165 in-lb. Planning strings, a battery bank or a service upgrade around the 18kPV? Our team is happy to help with sizing.
Recommended Accessories
Frequently Asked Questions
The 18kPV is the bigger unit in every direction: 12kW of continuous output versus 8kW, 18kW of usable solar on three MPPTs versus 12kW on two, 250A of battery charging versus 167A, and 200A of grid pass-through versus 80A. The 12kPV weighs 110 lb against the 18kPV's 121 lb and fits homes whose loads and service stay within its 80A pass-through.
Yes. When the grid fails, the 18kPV switches its backed-up loads to battery and solar in 20ms by default, or 10ms when configured. Paralleled units transfer in 20ms. No separate automatic transfer switch is needed for the loads wired through it.
EG4 calls for a 120/240V, 60Hz generator between 6kW and 21.6kW with under 3% THD. The 2-wire start relay (30Vdc or 277Vac max) can start it automatically on low battery voltage or state of charge, on a grid outage once the battery reaches its cutoff, or on a forced charge request. You can also enter the generator's rated power so the inverter never asks it for more than it can deliver.
EG4's LL, WallMount and LifePower4 batteries all communicate with the 18kPV (LifePower4 V1 needs a firmware update first). EG4's compatibility list also includes Pylontech (US2000, US3000 and UP5000), Pytes (E-BOX-48100R), UZ Energy, GSL Energy and Fortress Power, among others. Batteries outside the list can still run on voltage-based settings. EG4 recommends at least 300Ah of battery per inverter.
Yes. The 18kPV supports 120/208V service (L1, L2 and neutral required) at 10.4kW per unit, and EG4 publishes a three-phase configuration wiring diagram for paralleled units. EG4 recommends having a qualified professional review the change to the 120/208V setting.