Victron Quattro 48/15000 15kVA 230V Inverter Charger, 12kW Continuous, 25kW Surge, 200A Charger, Dual AC Inputs, 240V 60Hz, 120/240V With Autotransformer
SKU: QUA483150000







Log in to check member price and detailed stock information.
| Need more than what's available? Tell us what you need and we can source it for you. |
Product Summary
The Victron Quattro 15kVA (model 48/15000) runs a whole off-grid home, shop or backup system from one 48V inverter charger, with 25kW of surge for well pumps, compressors and welders. Set it to 240V at 60Hz to power US 240V loads directly, or add a Victron Autotransformer for full 120/240V split phase.
Specifications:
-
15,000VA (12,000W) continuous at 77°F (25°C), 10,000W at 104°F (40°C) and 25,000W peak
-
48V battery input (38 to 60Vdc) with a 200A lithium-compatible charger
-
Two AC inputs rated 100A each (187 to 250Vac, 50/60Hz) with a built-in transfer switch
-
Ships at 230V 50Hz and sets to 240V 60Hz for US 240V loads
-
Main output switches to battery in under 20 milliseconds, plus a 50A second output that runs only on grid or generator power
-
Scales to 12 units in three phase (four sets of three) for 180kVA
-
96% peak efficiency, 110W at idle or 20W in search mode
-
159 lb (72 kg), 22.5 x 19.2 x 13.5 in (572 x 488 x 344 mm) H×W×D, with a 5-year warranty

Current Connected is YOUR Victron product specialist
About the Victron Quattro 48/15000 15kVA Inverter Charger
15kVA is as big as Victron's inverter chargers get, and this Quattro puts all of it in one 48V unit: 12kW continuous, 25kW of surge and a 200A charger. If you're shopping for a 15kW Victron inverter to run a whole home, shop or ranch, this is it, and the 230V version runs US 240V circuits from a single box.
The surge rating is where it earns its keep. Well pumps, air compressors, welders and big mini-splits pull several times their running current at startup, and 25kW of peak power gives them the headroom to start. The low frequency design handles those inductive loads, and the pure sine output keeps computers and other sensitive electronics running clean.
Victron 240V Inverter for Well Pumps, Shops and Off-Grid Homes
Out of the box the Quattro runs 230V at 50Hz. Set it to 240V at 60Hz and it feeds US 240V loads straight from its output: well pumps, shop compressors, welders, EV chargers and 240V mini-splits, all from one inverter with nothing to stack. The setting change takes the MK3-USB interface and Victron's configuration software on a laptop.
The AC inputs suit US service too. Each one accepts 187 to 250Vac at 50 or 60Hz, so 240V from the grid or a generator falls right inside its range.
120/240V Split Phase From One Quattro and an Autotransformer
Need 120V circuits too? Add a Victron Autotransformer and one Quattro supplies a full 120/240V split-phase panel, a pairing Victron calls out in the Quattro datasheet. The Autotransformer creates the neutral, houses the relay that bonds neutral to ground, and shifts power between legs as 120V loads switch on and off.
On the current 50A and 100A models, the transformer moves up to 45A between legs continuously (55A for 30 minutes). Put the heavy hitters on 240V circuits (well pump, water heater, range, dryer, HVAC), spread the 120V loads across both legs, and that 45A goes a long way.
Planning the panel layout? Our team is happy to help with sizing.
Two 100A AC Inputs for Grid and Generator
The Quattro takes two AC sources, such as the grid and a generator or two generators, and switches to whichever one is live. Each input passes up to 100A through to your loads. PowerControl caps what the Quattro pulls from a small generator so charging only uses what the loads leave spare, and PowerAssist adds battery power on top of a weak source when a big load kicks on.
When the grid or generator drops, the main output switches to battery in under 20 milliseconds, fast enough that computers keep running. A second output stays live only while AC is present, so a water heater or other heavy load runs on generator time instead of draining the battery.
Three Phase and Parallel Systems up to 180kVA
Three Quattros configure for three-phase output, and up to four sets of three run in parallel for 144kW (180kVA) of inverter power and 2,400A of charging. Victron's configuration software handles the parallel and three-phase setup. For 277/480V commercial service, the Quattro 15kVA 277V brings the same 15kVA platform to US three phase.
Battery Cables, Fusing and Installation
Victron's manual calls for installation by a qualified electrician, and most of the job is heavy DC wiring. The Quattro draws up to 350A from the battery, so Victron specifies a 600A DC fuse (a Class T fuse belongs here) and two positive and two negative cables, each 95 mm² for runs up to 16 ft (5 m). 4/0 AWG is the closest US size that meets that, and our custom battery cables come built to your exact length.
The cables land on four M8 bolts, torqued to 10 ft-lb (14 Nm) maximum. Mount the Quattro vertically on a solid wall such as concrete or masonry, indoors (IP20), with at least 4 in (10 cm) of clear space around it for cooling. Keep it close to the batteries but never directly above them, and plan the lift for 159 lb (72 kg).
Recommended Accessories
Frequently Asked Questions
Yes, two ways. Victron's 230V models, this Quattro included, switch to 240V at 60Hz in software. Its 120V models reach 240V in pairs stacked for split phase, or one at a time stepped up through an Autotransformer.
Victron describes the Quattro as a MultiPlus with a second AC input. The MultiPlus connects to one AC source, while the Quattro connects to two, like the grid and a generator, and switches between them on its own. For a system with both, that second input saves you a separate transfer switch and the wiring that goes with it.
Two Quattro 48/10000 120V units stacked in split phase give 20kVA, and since each leg has its own inverter, the 120V loads can run as unbalanced as each unit allows. One 230V Quattro with an Autotransformer delivers 15kVA from a single unit, with one set of battery cables to run and one inverter to set up. Systems with mostly 240V loads lean toward the single Quattro; systems heavy on 120V loads lean toward the pair.
No. Victron certifies the 230V Quattro to IEC and EN standards, including IEC 62109-1 and IEC 62040-1, and carries UL 1741 on its 120V Quattros. It fits off-grid systems and any site where the AHJ (Authority Having Jurisdiction) accepts IEC-certified equipment. Where UL listing is required, a split-phase pair of Quattro 48/10000 120V units, which carry UL 1741, covers the same ground.
Yes. Add a GX device such as the Ekrano GX or Cerbo GX and the whole system reports to Victron's VRM portal, free of charge, from anywhere with an internet connection. Over Ethernet, the GX device also lets you change settings remotely.
Yes. Victron rates the Quattro as lithium-ion compatible, and its charge voltages adjust in the configuration software to match your battery manufacturer's settings.
Customer Reviews